Wave Dynamics AcousticsBuilding Services Noise and Vibration Control
We assess and control noise and vibration from mechanical and electrical plant, so occupied rooms meet their design criteria and neighbours are protected from external plant noise.
We assess and control noise and vibration from mechanical and electrical plant, so occupied rooms meet their design criteria and neighbours are protected from external plant noise.
Heating, ventilation and air conditioning systems, pumps, generators, lifts and electrical plant all produce noise and vibration. If these are not considered during design, the result can be noisy offices, disturbed hotel guests, complaints from neighbours or failed planning conditions. Building services noise control means setting suitable limits, checking the design against them and specifying the measures needed to meet them.
We work with mechanical and electrical engineers, architects and contractors on new buildings, refurbishments and fit-outs. Our project work includes specifying noise and vibration control for building services in historic venues, mechanical services noise assessments for hotels, and plant noise work for data centres.
The first step is agreeing what each space needs. Internal noise from building services is usually expressed as a Noise Rating (NR) value or an A-weighted level, chosen to suit the use of the room. A recording studio, a hotel bedroom and an open plan office need very different limits.
We draw on established guidance when proposing criteria, including:
Agreeing criteria early gives the design team a clear target and avoids costly changes later.
Once criteria are set, we review the mechanical design and calculate the noise reaching each sensitive room. This includes sound power data for fans and air handling units, regenerated noise at bends, dampers and grilles, duct breakout, and crosstalk between rooms through shared ductwork.
Where the predicted levels exceed the criteria, we recommend practical measures such as attenuators, lined ductwork, reduced air velocities, acoustic enclosures or relocating plant. We aim to recommend the simplest measure that works, so that space, cost and pressure drop are kept under control. Calculations are issued in a format the services engineer can check and update as the design develops. Where plant selections change at tender stage, we rerun the affected calculations so the attenuation still matches the equipment actually being installed.
Rooftop chillers, condensers, extract fans and standby generators can affect nearby homes and businesses. Planning authorities often set conditions limiting noise from new plant, and these are commonly assessed using BS 4142:2014+A1:2019, which compares the rating level of the plant with the existing background sound level.
We measure background levels, predict plant noise at the nearest receptors and advise on screens, enclosures, attenuators or plant selection. This work links closely with our plant noise assessments and planning assessments. For larger sites, such as data centres with many units operating together, we use noise modelling to test different layouts before they are fixed.
Rotating and reciprocating equipment passes vibration into the building structure. This can be felt in floors or heard as structure-borne noise in rooms some distance from the plant. Rooftop plant above bedrooms and plant rooms next to offices are common problem areas.
We specify vibration isolation to suit the equipment and the supporting structure, including:
Isolators only work when the natural frequency of the mounted system is well below the forcing frequency of the equipment, so selection must be based on actual operating data.
Good acoustic design can be undone on site. Attenuators are sometimes value engineered out, isolators are left locked down after installation, and ducts or pipes are rigidly fixed to sensitive walls and ceilings. Penetrations through separating walls and floors may also be left unsealed, creating paths for noise between rooms.
We can review contractor submittals for attenuators, isolators and plant selections to confirm they match the acoustic specification. Where a substitution is proposed, we check whether the alternative still meets the criteria. Site inspections at key stages, before ceilings are closed, allow problems to be corrected while access is still easy and costs are low.
Older buildings bring extra constraints. There may be limited space for attenuators, restrictions on fixing to historic fabric, and lightweight floors that transmit vibration easily. Performance spaces, conference venues and listening rooms also need very low background noise so speech and music are not masked.
In these settings we work closely with conservation architects and services engineers to find routes, plant locations and isolation details that meet the acoustic targets without unnecessary intervention in the building fabric. Early involvement is particularly useful, because plant locations are hard to change once they are agreed.
Before handover, we can measure building services noise in completed rooms to check compliance with the agreed criteria. Measurements are taken with systems operating at their normal duty, and results are reported against the specification.
Where levels are too high, the measurements help identify the cause, such as an undersized attenuator, a fan running faster than designed or a short circuited isolator. We then advise on targeted remedial work. If a problem is reported after occupation, our noise and vibration complaint investigations follow a similar process.
A Noise Rating is a single number that describes background noise by comparing measured octave band levels against a set of standard curves. It takes account of the frequency content of the noise, which makes it useful for building services, where low frequency fan and duct noise can be more noticeable than an A-weighted level suggests.
Ideally at concept or early design stage, when plant locations, riser sizes and duct routes are still being decided. At this point attenuators and isolation can be allowed for without redesign. Involvement only at tender or construction stage often limits the options to more expensive or less effective measures.
Typically we need plant schedules with sound power data, fan duty points, duct layouts and sizes, grille and diffuser schedules, plant locations and room uses. Manufacturer octave band data gives the most reliable results. Where data is not yet available, we can use typical values and update the calculations later.
Often it can, although the options are usually more limited. Common fixes include adding attenuators, fitting enclosures or barriers, replacing failed or wrongly selected isolators and adjusting fan speeds. Measurements on site help confirm the cause first, so the remedial work is targeted and not based on guesswork.
Building Regulations sound insulation requirements in Ireland and the UK focus mainly on separating walls and floors rather than plant noise. However, building services noise is often covered by planning conditions, client specifications, BREEAM credits and sector guidance for buildings such as schools and hospitals, so it still needs to be designed for.
Yes. Standby generators usually run only during testing and power failures, so the assessment approach depends on how often they operate and what the planning authority requires. We consider routine test runs separately from emergency use and advise on enclosures, exhaust silencers and scheduling of tests to limit disturbance.